Zanotti Refrigeration Error Codes: GM, SP O and DB O Alarms

Zanotti Refrigeration Error Codes: GM, SP O and DB O Alarms
Ali ElmCold Room

Zanotti alarm codes depend on the range. On GM Uniblock units, E1 is the room sensor, E2 the evaporator sensor, E3 the condenser sensor and nPA a high pressure alarm. On SP O and DB O units, E0 is the room sensor, E1 the evaporator sensor, and HH and PP are high pressure alarms, with PP stopping the unit after more than 10 trips in an hour. HI means high temperature on all of them.

The tables below come from Zanotti's own use and maintenance manuals, including the GM Uniblock manual now published in Daikin UK's document library. Check the range on the unit's rating plate first, because E1 means a different sensor on GM than on SP O and DB O.

At a glance

CodeRangeWhat Zanotti says it means
E1GMRoom sensor
E0SP O, DB ORoom sensor
E1SP O, DB OEvaporator sensor
HIAllHigh temperature
nPAGMHigh pressure. More than 10 trips in 1 hour turns the unit off
PPSP O, DB OMore than 10 high pressure trips in one hour. All functions interrupted
EA, AMGM (EA), SP O and DB O (AM)Voltage monitor: supply voltage outside plus or minus 12%

Source: Zanotti GM Uniblock installation and operation manual (0MAN106M), and Zanotti SP O and DB O use and maintenance manuals.

How Zanotti shows an alarm

On GM Uniblock units, Zanotti's installation and operation manual says an alarm switches on the red alarm LED and, depending on the alarm, the alarm relay. Pressing any key mutes the relay, and the LED keeps flashing while the alarm condition is present. To see the code, press the PRG key, and AL appears. Press PRG again, and the code for the cause of the alarm is displayed. To leave the alarm menu, wait 15 seconds or press and release ON/OFF.

On SP O and DB O units, the code is shown on the display, usually alternating with the cold room temperature.

Zanotti GM Uniblock codes

CodeWhat Zanotti says it meansWhat happens
HIHigh temperature (listed as AH1)Red LED and alarm relay on. HI shown in the alarm menu
AL1Low temperatureRed LED and alarm relay on. AL1 shown in the alarm menu
E1Room sensorRed LED and alarm relay on. E1 displayed
E2Evaporator sensorRed LED and alarm relay on. E2 and the cold room temperature shown alternately
E3Condenser sensorRed LED and alarm relay on. E3 and the cold room temperature shown alternately
AH3Condenser temperature above a factory pre-set valueRed LED on. AH3 shown in the alarm menu
nPAHigh pressureRed LED on each time the pressure switch trips. More than 10 trips in 1 hour turns the unit off and activates the alarm relay
EAVoltage monitor: supply voltage varying by more than plus or minus 12%The unit stops for about 6 minutes, then restarts automatically if the voltage is within limits
OpdDoor alarm: the door contact has been open for more than 60 minutes (translated from German in the manual)The unit starts running again
E8The keyboard is not recognisedShown on newer GM revisions
ONThe room light is onNot a fault. ON alternates with the temperature

Zanotti SP O and DB O codes

These come from Zanotti's SP O use and maintenance manual and its DB O manual, which share the same alarm list.

CodeWhat Zanotti says it meansCause and remedy
HIHigh temperature, alternating with the cold room temperatureSee the checks below
LOLow temperature, alternating with the cold room temperatureSee the checks below
E0Room sensor, shown steadySensor not connected. Replace sensor
E1Evaporator sensor, alternating with the cold room temperatureSensor not connected. Replace sensor
HHHigh pressure, alternating with the room temperature. LED 4 lights each time the high pressure switch tripsFaulty condenser fan or dirty condenser. Switch off, wait a few seconds and switch on again
PPMore than 10 high pressure trips in one hour. Alarm relay and LED 4 on, all functions interruptedAs for HH
AMVoltage monitor: supply voltage varying by more than plus or minus 12%The unit stops for about 6 minutes, then restarts automatically if the voltage is within limits

Zanotti adds a note for the voltage monitor: when the unit is first started, the monitor runs a 7-minute counting phase, during which the unit should be left connected but switched off.

Why E1 means two different things

The most common mix-up with Zanotti codes is E1. On a GM Uniblock, E1 is the room sensor, so the controller has lost the reading it uses to hold the room at temperature. On an SP O or DB O, the room sensor is E0 and E1 is the evaporator sensor, which matters more for defrosting than for day-to-day temperature control. Either way it is a sensor fault for an engineer, but knowing which sensor tells you how closely to watch the stock in the meantime.

Zanotti transport units

Zanotti's vehicle refrigeration units, such as the Zer0 range, use a different set of alarms, including PrL, PR1, Prh, PRS, Ab and rSt. Zanotti Transblock publishes that list of Zer0 alarms and messages, with possible causes and what the user can do. Those are not the same as the cold room codes on this page.

How to reset a Zanotti alarm

  • Mute. Press any key to mute the alarm relay. The LED keeps flashing until the cause clears.
  • High pressure lock-out. For nPA on a GM, Zanotti says to turn the unit off and then on again. For HH and PP on SP O and DB O, switch off, wait a few seconds and switch on again.
  • Voltage. EA and AM clear themselves: the unit restarts after about 6 minutes if the supply is back within limits.

A reset after a high pressure lock-out only helps if the cause has gone. Zanotti names a faulty condenser fan and a dirty condenser, so if the alarm returns, that is where an engineer will look.

What you can check safely

Zanotti's SP O manual lists checks for a room that will not hold temperature when no fault is found in the unit:

  • The cold room doors close tightly and there is no loss of cold.
  • The room is used sensibly, with no unfrozen liquids or foods placed in a low temperature room.
  • The evaporator is free of ice.

If ice is building up on the evaporator, Zanotti lists the door being opened too often, a faulty evaporator fan, a faulty solenoid valve on hot gas defrost models, a faulty defrost heater on electric defrost models, or a faulty defrost process. If the display does not light at all, check there is power to the unit, the mains cable is connected and the fuses in the electric panel are intact.

Safety

  • Zanotti warns never to use hot water or pointed, cutting or metal objects to remove ice.
  • Removing the protective guards while the machine is running is forbidden.
  • Maintenance should be carried out by trained personnel or the manufacturer under EN 378, and worn parts replaced only by qualified personnel.
  • Switch off before working on the unit, because of the danger of electrocution.
  • Refrigerant must never be released into the atmosphere and must be recovered by specialised technicians, which in the UK means an engineer with the F gas qualifications set out by GOV.UK.

When to call an engineer

  • Any sensor fault: E1, E2 or E3 on a GM, or E0 and E1 on an SP O or DB O.
  • nPA or PP lock-outs, or HH that keeps appearing.
  • AH3, which points to the condenser running too hot.
  • EA or AM that keeps returning, which points to the supply.
  • HI that returns with the door shut and the evaporator clear of ice.

Our cold room repair team works on Zanotti units across London, and our comparison of monoblock and split systems explains how units like the GM Uniblock work.

Questions people ask about Zanotti error codes

What does E1 mean on a Zanotti unit?

On a GM Uniblock, E1 is a room sensor fault. On SP O and DB O units, E1 is an evaporator sensor fault and the room sensor is E0. Both need an engineer to check or replace the sensor.

What does nPA mean on a Zanotti?

nPA is the high pressure alarm on GM units. The red LED lights each time the high pressure switch trips, and more than 10 trips in an hour turns the unit off. Turn it off and on again to reset it, but a dirty condenser or a condenser fan fault is the likely cause.

What does PP mean on a Zanotti?

On SP O and DB O units, PP means the high pressure switch has tripped more than 10 times in an hour, so the alarm relay is on and all functions have stopped. Zanotti names a faulty condenser fan or a dirty condenser as the causes.

How do I reset a Zanotti refrigeration unit?

Press any key to mute the alarm. For a high pressure lock-out, switch the unit off, wait a few seconds and switch it on again. If the alarm returns, the cause is still there and needs an engineer.

What does EA or AM mean on a Zanotti?

EA on a GM and AM on SP O and DB O units are voltage monitor alarms: the supply voltage has varied by more than 12%. The unit stops for about 6 minutes and restarts automatically once the voltage is back within limits.

Where can I find a Zanotti manual?

The GM Uniblock manual is in Daikin UK's online document library. Use the model on the unit's rating plate to find the right one, and quote that number when ordering spare parts.

Keeping a Zanotti cold room running

Find the range, read the code, and work through Zanotti's own checks: doors, ice on the evaporator and a clean condenser. Sensor faults and repeated pressure lock-outs need an engineer, and planned refrigeration maintenance keeps condensers clean before they cause a high pressure alarm.

Last updated: 4 November 2026

Ali Elm, Head of Operations at Be Cool Refrigeration

Written by

Ali Elm

Ali is the Head of Operations at Be Cool Refrigeration with over a decade of hands-on experience in HVAC and commercial refrigeration. He oversees every installation, repair, and maintenance project, making sure the work meets the highest standards. Ali holds full F-Gas certification and has worked across residential, commercial, and industrial refrigeration systems throughout London and the South East. When he is not on site, he writes these guides to help business owners and homeowners understand their cooling systems better.