Hoshizaki Ice Machine error codes

If faults are occurring on your Hoshizaki Ice Maker, it is very important to discover it quickly. Error codes are a great way to find out the initial problem. Error codes are usually displayed on the controller.

If you can’t find what you are looking for, give us a call on 0203 488 1889 and we will be happy to help.

Hoshizaki Ice Machine error codes:

Error Code Problem Corrective Action/Reset Details
E1 Freeze Cycle Backup Timer

Freeze cycle backup timer (Control Board Setting 6) has terminated.

45 min. after water tank starts to close in preceding harvest cycle, unit stops if the evaporator temperature is above 32°F (0°C).

Check for inlet water valve leaking by, hot gas valve leaking by, pump motor not pumping, thermostatic expansion valve not feeding properly, low charge, or inefficient compressor.

 

Press the “RESET” button to reset.

E2 Harvest Cycle Backup Timer

Harvest cycle backup timer has terminated.

30 min. after water tank starts to open in harvest cycle, unit stops if harvest cycle termination temperature (Control Board Setting 1) has not been reached.

Check for open thermistor, HGV not opening, TXV leaking by, low charge, or inefficient compressor.

 

Press the “RESET” button to reset.

EE

(E3)

Water Tank Opening Backup Timer

3-minute opening backup timer starts when water tank starts to open.

If actuator motor’s internal position sensor does not indicate water tank is fully open within

3 minutes, display shows “EE” and unit stops for 60 minutes.

If error recurs after unit resumes operation,

display shows “EE” and unit shuts down.

Check actuator motor and control board. Press the “RESET” button to reset.
EE

(E4)

Water Tank Closing Backup Timer

3-minute closing backup timer starts when water tank starts to close.

If actuator motor’s internal position sensor does not indicate water tank is fully closed within

3 minutes, display shows “EE” and unit stops for 60 minutes.

If error recurs after unit resumes operation,

display shows “EE” and unit shuts down.

Check actuator motor and control board. Press the “RESET” button to reset.
EE

(E5)

High Evaporator Temperature

If evaporator temperature 140°F (60°C) or higher for 5 sec., unit stops.

Check for harvest problem (stuck HGV or control board relay), hot water entering unit, or shorted thermistor.

 

Press the “RESET” button to reset.

EE

(E9)

Condenser Thermistor Error

If condenser thermistor is open or shorted for 2 sec., unit stops.

Note: IM-500SAA does not utilize a condenser

thermistor, therefore E9 error will not occur.

Replace condenser thermistor.
EE

(EA)

Control Board Error

If model data IC is defective, unit stops.

Replace control board.
EE

(EC)

Evaporator (Cube Control) Thermistor Error If evaporator thermistor is open or shorted for 2 sec., unit stops. Replace evaporator thermistor.
EE

(Ed)

Water Regulating Valve Error

If water regulating valve thermistor detects a temperature below the water regulating valve error detection temperature (Control Board Setting 36), error is displayed but unit continues to operate.

Note: IM-500SAA does not utilize a water

regulating valve, therefore Ed error will not occur.

Check water regulating valve. Press the “RESET” button to reset.

Eliwell ID or UniCold error codes

If faults are occurring on your Eliwell Fridge or Freezer Controller, that being Eliwell ID or Eliwell UniCold, it is very important to discover it quickly. Error codes are a great way to find out the initial problem. Error codes are usually displayed on the controller.

If you can’t find what you are looking for, give us a call on 0203 488 1889 and we will be happy to help.

Eliwell ID or UniCold error codes:

Label Description Effects
E1 Probe Pb1 in error • Label E1 displayed

• Alarm icon permanently ON

• Controller disabled maximum/minimum alarms

• Compressor operation based on parameters Ont and OFt.

E2 Probe Pb2 in error • Label E2 displayed

• Alarm icon permanently ON

AH1 Alarm for HIGH Pb1

temperature

• Registration AH1 label in the

AL folder

• No effect on regulation

• Label AH1 displayed alternately with the actual value read by Pb1 probe

AL1 Alarm for LOW Pb1

temperature

• Registration AL1 label in the

AL folder

• No effect on regulation

• Label AL1 displayed alternately with the actual value read by Pb1 probe

EA External alarm • Registration EA label in the

AL folder

• Alarm icon permanently ON

• Regulation blocked if rLO=y

Carel SmartCella or UltraCella error codes

If faults are occurring on your Carel SmartCella or UltraCella Cold room, it is very important to discover it quickly. Error codes are a great way to find out the initial problem. Error codes are usually displayed on the controller.

If you can’t find what you are looking for, give us a call on 0203 488 1889 and we will be happy to help.

Carel SmartCella or UltraCella error codes:

Code on display Cause of the alarm
rE Virtual control probe fault
E0 Probe S1 fault
E1 Probe S2 fault
E2 Probe S3 fault
E3 Probe S4 fault
LO Low temperature alarm
HI High temperature alarm
AFr Frost protection alarm
IA Immediate alarm from external contact
dA Delayed alarm from external contact
Pd Alarm maximum pump down time
LP Low pressure alarm
AtS Autostart in pump down
cht High condenser temp. pre-

alarm

CHt High condenser temperature alarm
dor Door open for too long alarm
EE Unit parameter EEPROM error
EF Operating parameter EEPROM error

Danfoss Refrigeration Error Codes

If faults are occurring on your Danfoss refrigeration system, it is very important to discover it quickly. Error codes are a great way to find out the initial problem. Error codes are usually displayed on the controller.

If you can’t find what you are looking for, give us a call on 0203 488 1889 and we will be happy to help.

Danfoss Refrigeration error codes:

Alarm code Possible cause Solution
E0 Cold room temperature sensor not working properly •         Check that cold room temperature sensor is working properly

•         If the problem persists replace the sensor

E1 Defrost sensor not working properly (In this case defrosts will last time d3) •         Check that defrost sensor is working properly

•         If the problems persists replace the sensor

E2 Eeprom alarm

An EEPROM memory alarm has been detected (All outputs except the alarm one are

deactivated)

•         Switch unit off and then back on again
E8 Man-in-room alarm •         Reset the alarm input inside the cold room
Ec Compressor protection tripped (e.g. thermal protection or max pressure switch)

(All outputs except the alarm one – where

applicable – are deactivated)

•         Check that compressor is working properly

•         Check compressor absorption

•         If the problem persists contact the technical

assistance

Ed Open door – alarm (Open door and tdo-time has expired) Check door / door contact
Temperature shown on display is flashing Minimum or maximum temperature alarm. The temperature inside the cold room has exceeded the min. or max. temperature alarm setting (see variables A1 and A2, user programming level) •         Check that the compressor is working properly.

•         Sensor not reading temperature properly or compressor start/stop control not working.