Danfoss Refrigeration Error Codes
If faults are occurring on your Danfoss refrigeration system, it is very important to discover it quickly. Error codes are a great way to find out the initial problem. Error codes are usually displayed on the controller.
If you can’t find what you are looking for, give us a call on 0203 488 1889 and we will be happy to help.
Danfoss Refrigeration error codes:
Alarm code | Possible cause | Solution |
E0 | Cold room temperature sensor not working properly | • Check that cold room temperature sensor is working properly
• If the problem persists replace the sensor |
E1 | Defrost sensor not working properly (In this case defrosts will last time d3) | • Check that defrost sensor is working properly
• If the problems persists replace the sensor |
E2 | Eeprom alarm
An EEPROM memory alarm has been detected (All outputs except the alarm one are deactivated) |
• Switch unit off and then back on again |
E8 | Man-in-room alarm | • Reset the alarm input inside the cold room |
Ec | Compressor protection tripped (e.g. thermal protection or max pressure switch)
(All outputs except the alarm one – where applicable – are deactivated) |
• Check that compressor is working properly
• Check compressor absorption • If the problem persists contact the technical assistance |
Ed | Open door – alarm (Open door and tdo-time has expired) | Check door / door contact |
Temperature shown on display is flashing | Minimum or maximum temperature alarm. The temperature inside the cold room has exceeded the min. or max. temperature alarm setting (see variables A1 and A2, user programming level) | • Check that the compressor is working properly.
• Sensor not reading temperature properly or compressor start/stop control not working. |