
Mitsubishi Heavy Industries shows faults two ways. Ducted, cassette and other PAC units display an E code on the wired remote, such as E5 for an indoor-outdoor communication fault or E57 for a refrigerant shortage. SRK wall units have no code display and flash their RUN and TIMER lights a set number of times instead.
Mitsubishi Heavy Industries is not the same company as Mitsubishi Electric, and its codes are not the same either. Mix the two up and an E6 sends the engineer looking at the wrong part. For this 2026 update we rebuilt every table on this page from Mitsubishi Heavy Industries' own published documents, so the meanings below are the manufacturer's, not a blog's best guess.
At a glance
| Question | Answer |
|---|---|
| Where do E codes show? | On the wired remote control of PAC indoor units such as FDT cassettes and FDU ducted units |
| Communication fault | E1 (remote control or connection wiring) and E5 (indoor-outdoor connection during operation) |
| Drain fault | E9, drain trouble: drain pump, float switch or their wiring |
| Refrigerant-related | E57, shortage in refrigerant quantity, or a closed service valve |
| Wall-mounted SRK units | No E code; the RUN and TIMER lights flash a set number of times |
| Different families | Inverter KX systems use some of the same numbers with different meanings |
Sources: Mitsubishi Heavy Industries Air-Conditioners Australia, Service Support Handbook and SRK ZSA series user manual
PAC indoor unit error codes
These are the indoor unit self-diagnosis codes from MHI's Service Support Handbook for its inverter PAC indoor units: FDT and FDTC cassettes, FDU, FDUA and FDUM ducted units, FDE/FDEN ceiling units and DXU. The handbook lists both the previous R410A and current R32 series in the same table.
| Code | Location of trouble | Description MHI gives |
|---|---|---|
| E1 | Remote control wires, indoor-outdoor connection wire | Poor connection of the remote control signal wire, electrical noise, or a defective remote control or control PCB |
| E5 | Indoor-outdoor unit's connection wire | Poor connection between the indoor and outdoor units during operation, or communication disturbed by noise; also a defective outdoor PCB or blown fuse |
| E6 | Indoor heat exchanger temperature thermistor | Defective thermistor, broken wire, short circuit or poor connector contact |
| E7 | Indoor return air temperature thermistor | Defective thermistor, broken wire, short circuit or poor connector contact |
| E8 | Installation or operating condition | Heating overload: anomalously high indoor heat exchanger temperature |
| E9 | Drain trouble | Defective drain pump, broken drain pump wire, disconnected connector, or float switch malfunction |
| E10 | Number of connected indoor units | More than 16 units under multi-unit control by one remote control |
| E11 | Address setting error | Address setting error of indoor units |
| E14 | Remote controller fault | No master assigned to slaves, incorrect wiring, or a broken wire between master and slave |
| E16 | Indoor fan motor | Faulty indoor fan motor, poor connection, faulty indoor PCB or poor neutral connection |
| E19 | Indoor control PCB | Improper operation mode setting |
| E20 | Fan motor | Indoor fan motor rotation speed anomaly |
| E21 | Panel switch detection | Defective or open filter panel switch (FDT only) |
| E28 | Remote control temperature thermistor | Broken wire of the remote control temperature thermistor |
Source: MHI Service Support Handbook, PAC indoor unit self-diagnosis information
PAC outdoor unit error codes
The outdoor codes for the same family (FDC, FDCA and FDCVA outdoor units, plus DXC) cover the power supply, sensors, pressures and the compressor. Several of them list a closed service valve as a cause, which is an installation or maintenance issue rather than a broken part.
| Code | Description MHI gives |
|---|---|
| E33 | Anomalous current on the inverter primary side (power supply) |
| E34 | Phase open circuit or rotation, faulty outdoor control PCB (3 phase); incorrect DIP switch (single phase) |
| E35 | Higher outdoor heat exchanger temperature, or a defective outdoor heat exchanger thermistor |
| E36 | Higher discharge temperature, or a defective discharge pipe thermistor |
| E37 | Defective outdoor heat exchanger thermistor, broken wire or poor connection |
| E38 | Defective outdoor air temperature thermistor, broken wire or poor connection |
| E39 | Defective discharge pipe temperature thermistor, broken wire or poor connection |
| E40 | Rising high pressure (operation of 63H1): service valve closed, or poor airflow in heating |
| E41 | Power transistor overheat |
| E42 | Current cut (anomalous compressor over-current), or service valve closed |
| E44 | Liquid back error in cooling mode; the compressor stops if it is detected 3 times within 90 minutes |
| E45 | Anomalous outdoor control PCB or inverter PCB communication |
| E47 | Anomalous inverter over voltage |
| E48 | Anomalous outdoor fan motor |
| E49 | Low pressure error, service valve closed, or a fault with the low pressure sensor |
| E51 | Anomalous inverter PCB |
| E53 | Defective suction pipe temperature thermistor, broken wire or poor connection |
| E54 | Defective low pressure sensor |
| E55 | Under-dome temperature thermistor: poor connection, broken wire, faulty thermistor or PCB |
| E57 | Shortage in refrigerant quantity, or service valve closed |
| E59 | Anomalous compressor start-up |
| E60 | Faulty compressor or faulty inverter circuit |
| E75 | Central controller communication error |
Source: MHI Service Support Handbook, PAC outdoor unit self-diagnosis information
E57 is the one people tend to want an easy answer to. MHI gives two causes: not enough refrigerant, or a service valve left closed. Either way, the fix starts with finding out why, not with adding gas.
SRK wall-mounted units: the flashing light codes
SRK wall units do not show an E code. MHI's user manual for the SRK ZSA series uses the RUN and TIMER lights instead. Count the flashes on one light while noting what the other is doing.
| Lights | Flashes | Description of trouble MHI gives |
|---|---|---|
| TIMER on, RUN flashing | 1 | Indoor heat exchanger sensor 1 error |
| TIMER on, RUN flashing | 2 | Room temperature sensor error |
| TIMER on, RUN flashing | 3 | Indoor heat exchanger sensor 3 error |
| TIMER on, RUN flashing | 5 | Circuit error |
| TIMER on, RUN flashing | 6 | Indoor fan motor error |
| TIMER on, RUN flashing | 7 | Refrigerant is insufficient, or closed service valve |
| RUN keeps flashing, TIMER flashing | 1 | Outdoor temperature sensor error |
| RUN keeps flashing, TIMER flashing | 2 | Outdoor heat exchanger sensor error |
| RUN keeps flashing, TIMER flashing | 4 | Discharge pipe sensor error |
| RUN keeps flashing, TIMER flashing | 5 | Suction pipe sensor error |
| RUN on, TIMER flashing | 1 | Current cut |
| RUN on, TIMER flashing | 2 | Trouble of outdoor unit |
| RUN on, TIMER flashing | 3 | Over current |
| RUN on, TIMER flashing | 4 | Power transistor error |
| RUN on, TIMER flashing | 5 | Over heat of compressor |
| RUN on, TIMER flashing | 6 | Error of signal transmission |
| RUN on, TIMER flashing | 7 | Outdoor fan motor error |
| RUN on, TIMER keeps flashing | Continuous | Cooling high pressure protection |
| RUN 2 flashes, TIMER flashing | 2 | Rotor lock |
| RUN 7 flashes, TIMER flashing | 1 | Closed service valve |
Source: MHI SRK20, 25, 35, 50ZSA-W user manual, Self diagnosis function
KX systems use the same numbers differently
MHI's handbook has a separate self-diagnosis table for its Inverter KX systems (KX4, KX6, KXZ and related models), and it reuses several E numbers with different meanings. That is exactly why a code should always be read against the right family.
| Code | Inverter KX meaning (MHI handbook) | PAC meaning, for comparison |
|---|---|---|
| E1 | Communication error between indoor unit and remote control | Remote control wires or indoor-outdoor connection wire |
| E2 | Duplicated indoor unit address | Not listed |
| E3 | Outdoor unit signal line error | Not listed |
| E10 | More than 17 indoor units controlled by one remote control | More than 16 units under one remote |
| E12 | Address setting error by mixed setting method | Not listed |
| E18 | Address setting error of master and slave indoor units | Not listed |
| E19 | Indoor unit operation check, drain motor check mode anomaly (switch left in check mode) | Improper operation mode setting |
Source: MHI Service Support Handbook, KX self-diagnosis information
Treat these tables as a fast way to understand a code, not a substitute for the technical manual for your exact model.
What you can check, and what needs an engineer
A few MHI codes point at something a site team can look at. E10, E11 and E14 are set-up problems with remotes and addresses rather than broken parts. E9 on a cassette means water is not leaving the unit, so a dripping ceiling tile alongside it is no coincidence, and our guide to air conditioning leaking water explains why. The rest are thermistors, boards, pressures, the compressor and the refrigerant circuit.
That second group is engineer work. On the refrigerant side it is also the law: GOV.UK states that "You must have your own qualifications to work on equipment containing F gas, even if you work for someone else." A cassette showing E57 needs leak finding by a qualified engineer, and if the system is large enough it will also be due regular leak checks under the same rules.
| Frequency of leak checks | Equipment contains (tonnes CO2 equivalent) | Equivalent R410A charge |
|---|---|---|
| At least once every 12 months | 5 to less than 50 | 2.4kg |
| At least once every 6 months | 50 to less than 500 | 24kg |
| Automatic leak detection required | 500 or more | 240kg |
Sources: GOV.UK, Checking F gas equipment for leaks and GOV.UK, Qualifications to work with F gas
When to call an engineer
If a code returns after a restart, or it is anything from the outdoor unit table, book a diagnosis. Be Cool's F-Gas certified engineers have worked on commercial air conditioning across London and the South East since 2004, and our air conditioning repair service covers Mitsubishi Heavy Industries cassettes, ducted units and wall units. Note the code, the model number and whether it appeared in heating or cooling before you call.
Frequently asked questions
What does E5 mean on a Mitsubishi Heavy Industries air conditioner?
On PAC units, MHI lists E5 as a poor connection of the wiring between the indoor and outdoor units during operation, or communication disturbed by electrical noise. A defective outdoor PCB or a blown fuse can also cause it.
What does E9 mean on a Mitsubishi Heavy cassette?
E9 is drain trouble: a defective drain pump, a broken drain pump wire, a disconnected connector or a float switch malfunction.
What does E57 mean on Mitsubishi Heavy Industries?
MHI lists E57 as a shortage in refrigerant quantity or a service valve left closed. It needs a qualified engineer.
My SRK wall unit is flashing. How do I read it?
Count the flashes of the RUN or TIMER light and note what the other light is doing, then match the pattern to MHI's table above. Seven RUN flashes with the TIMER light on, for example, means insufficient refrigerant or a closed service valve.
Are Mitsubishi Heavy Industries and Mitsubishi Electric codes the same?
No. They are different manufacturers with different code lists. If your unit is Mitsubishi Electric, see our Mitsubishi Electric error codes guide instead.
Get the family right first
With Mitsubishi Heavy Industries, the first question is not "what does E19 mean" but "which family is this unit". Answer that, read the code against the right table, and most faults point an engineer straight at the right part. For other brands, see our error code library.
About the author: Ali Elm runs Be Cool Refrigeration & Air Conditioning, a family-run London firm that has been installing, servicing and repairing commercial refrigeration and air conditioning since 2004. His F-Gas certified team has delivered more than 2,000 projects across London and the South East.
Last updated: 2 November 2026

Written by
Ali Elm
Ali is the Head of Operations at Be Cool Refrigeration with over a decade of hands-on experience in HVAC and commercial refrigeration. He oversees every installation, repair, and maintenance project, making sure the work meets the highest standards. Ali holds full F-Gas certification and has worked across residential, commercial, and industrial refrigeration systems throughout London and the South East. When he is not on site, he writes these guides to help business owners and homeowners understand their cooling systems better.