Mitsubishi Heavy Industries Error Codes (2026 Guide)

Mitsubishi Heavy Industries Error Codes (2026 Guide)
Ali ElmAC Error Codes

Mitsubishi Heavy Industries shows faults two ways. Ducted, cassette and other PAC units display an E code on the wired remote, such as E5 for an indoor-outdoor communication fault or E57 for a refrigerant shortage. SRK wall units have no code display and flash their RUN and TIMER lights a set number of times instead.

Mitsubishi Heavy Industries is not the same company as Mitsubishi Electric, and its codes are not the same either. Mix the two up and an E6 sends the engineer looking at the wrong part. For this 2026 update we rebuilt every table on this page from Mitsubishi Heavy Industries' own published documents, so the meanings below are the manufacturer's, not a blog's best guess.

At a glance

QuestionAnswer
Where do E codes show?On the wired remote control of PAC indoor units such as FDT cassettes and FDU ducted units
Communication faultE1 (remote control or connection wiring) and E5 (indoor-outdoor connection during operation)
Drain faultE9, drain trouble: drain pump, float switch or their wiring
Refrigerant-relatedE57, shortage in refrigerant quantity, or a closed service valve
Wall-mounted SRK unitsNo E code; the RUN and TIMER lights flash a set number of times
Different familiesInverter KX systems use some of the same numbers with different meanings

Sources: Mitsubishi Heavy Industries Air-Conditioners Australia, Service Support Handbook and SRK ZSA series user manual

PAC indoor unit error codes

These are the indoor unit self-diagnosis codes from MHI's Service Support Handbook for its inverter PAC indoor units: FDT and FDTC cassettes, FDU, FDUA and FDUM ducted units, FDE/FDEN ceiling units and DXU. The handbook lists both the previous R410A and current R32 series in the same table.

CodeLocation of troubleDescription MHI gives
E1Remote control wires, indoor-outdoor connection wirePoor connection of the remote control signal wire, electrical noise, or a defective remote control or control PCB
E5Indoor-outdoor unit's connection wirePoor connection between the indoor and outdoor units during operation, or communication disturbed by noise; also a defective outdoor PCB or blown fuse
E6Indoor heat exchanger temperature thermistorDefective thermistor, broken wire, short circuit or poor connector contact
E7Indoor return air temperature thermistorDefective thermistor, broken wire, short circuit or poor connector contact
E8Installation or operating conditionHeating overload: anomalously high indoor heat exchanger temperature
E9Drain troubleDefective drain pump, broken drain pump wire, disconnected connector, or float switch malfunction
E10Number of connected indoor unitsMore than 16 units under multi-unit control by one remote control
E11Address setting errorAddress setting error of indoor units
E14Remote controller faultNo master assigned to slaves, incorrect wiring, or a broken wire between master and slave
E16Indoor fan motorFaulty indoor fan motor, poor connection, faulty indoor PCB or poor neutral connection
E19Indoor control PCBImproper operation mode setting
E20Fan motorIndoor fan motor rotation speed anomaly
E21Panel switch detectionDefective or open filter panel switch (FDT only)
E28Remote control temperature thermistorBroken wire of the remote control temperature thermistor

Source: MHI Service Support Handbook, PAC indoor unit self-diagnosis information

PAC outdoor unit error codes

The outdoor codes for the same family (FDC, FDCA and FDCVA outdoor units, plus DXC) cover the power supply, sensors, pressures and the compressor. Several of them list a closed service valve as a cause, which is an installation or maintenance issue rather than a broken part.

CodeDescription MHI gives
E33Anomalous current on the inverter primary side (power supply)
E34Phase open circuit or rotation, faulty outdoor control PCB (3 phase); incorrect DIP switch (single phase)
E35Higher outdoor heat exchanger temperature, or a defective outdoor heat exchanger thermistor
E36Higher discharge temperature, or a defective discharge pipe thermistor
E37Defective outdoor heat exchanger thermistor, broken wire or poor connection
E38Defective outdoor air temperature thermistor, broken wire or poor connection
E39Defective discharge pipe temperature thermistor, broken wire or poor connection
E40Rising high pressure (operation of 63H1): service valve closed, or poor airflow in heating
E41Power transistor overheat
E42Current cut (anomalous compressor over-current), or service valve closed
E44Liquid back error in cooling mode; the compressor stops if it is detected 3 times within 90 minutes
E45Anomalous outdoor control PCB or inverter PCB communication
E47Anomalous inverter over voltage
E48Anomalous outdoor fan motor
E49Low pressure error, service valve closed, or a fault with the low pressure sensor
E51Anomalous inverter PCB
E53Defective suction pipe temperature thermistor, broken wire or poor connection
E54Defective low pressure sensor
E55Under-dome temperature thermistor: poor connection, broken wire, faulty thermistor or PCB
E57Shortage in refrigerant quantity, or service valve closed
E59Anomalous compressor start-up
E60Faulty compressor or faulty inverter circuit
E75Central controller communication error

Source: MHI Service Support Handbook, PAC outdoor unit self-diagnosis information

E57 is the one people tend to want an easy answer to. MHI gives two causes: not enough refrigerant, or a service valve left closed. Either way, the fix starts with finding out why, not with adding gas.

SRK wall-mounted units: the flashing light codes

SRK wall units do not show an E code. MHI's user manual for the SRK ZSA series uses the RUN and TIMER lights instead. Count the flashes on one light while noting what the other is doing.

LightsFlashesDescription of trouble MHI gives
TIMER on, RUN flashing1Indoor heat exchanger sensor 1 error
TIMER on, RUN flashing2Room temperature sensor error
TIMER on, RUN flashing3Indoor heat exchanger sensor 3 error
TIMER on, RUN flashing5Circuit error
TIMER on, RUN flashing6Indoor fan motor error
TIMER on, RUN flashing7Refrigerant is insufficient, or closed service valve
RUN keeps flashing, TIMER flashing1Outdoor temperature sensor error
RUN keeps flashing, TIMER flashing2Outdoor heat exchanger sensor error
RUN keeps flashing, TIMER flashing4Discharge pipe sensor error
RUN keeps flashing, TIMER flashing5Suction pipe sensor error
RUN on, TIMER flashing1Current cut
RUN on, TIMER flashing2Trouble of outdoor unit
RUN on, TIMER flashing3Over current
RUN on, TIMER flashing4Power transistor error
RUN on, TIMER flashing5Over heat of compressor
RUN on, TIMER flashing6Error of signal transmission
RUN on, TIMER flashing7Outdoor fan motor error
RUN on, TIMER keeps flashingContinuousCooling high pressure protection
RUN 2 flashes, TIMER flashing2Rotor lock
RUN 7 flashes, TIMER flashing1Closed service valve

Source: MHI SRK20, 25, 35, 50ZSA-W user manual, Self diagnosis function

KX systems use the same numbers differently

MHI's handbook has a separate self-diagnosis table for its Inverter KX systems (KX4, KX6, KXZ and related models), and it reuses several E numbers with different meanings. That is exactly why a code should always be read against the right family.

CodeInverter KX meaning (MHI handbook)PAC meaning, for comparison
E1Communication error between indoor unit and remote controlRemote control wires or indoor-outdoor connection wire
E2Duplicated indoor unit addressNot listed
E3Outdoor unit signal line errorNot listed
E10More than 17 indoor units controlled by one remote controlMore than 16 units under one remote
E12Address setting error by mixed setting methodNot listed
E18Address setting error of master and slave indoor unitsNot listed
E19Indoor unit operation check, drain motor check mode anomaly (switch left in check mode)Improper operation mode setting

Source: MHI Service Support Handbook, KX self-diagnosis information

Treat these tables as a fast way to understand a code, not a substitute for the technical manual for your exact model.

What you can check, and what needs an engineer

A few MHI codes point at something a site team can look at. E10, E11 and E14 are set-up problems with remotes and addresses rather than broken parts. E9 on a cassette means water is not leaving the unit, so a dripping ceiling tile alongside it is no coincidence, and our guide to air conditioning leaking water explains why. The rest are thermistors, boards, pressures, the compressor and the refrigerant circuit.

That second group is engineer work. On the refrigerant side it is also the law: GOV.UK states that "You must have your own qualifications to work on equipment containing F gas, even if you work for someone else." A cassette showing E57 needs leak finding by a qualified engineer, and if the system is large enough it will also be due regular leak checks under the same rules.

Frequency of leak checksEquipment contains (tonnes CO2 equivalent)Equivalent R410A charge
At least once every 12 months5 to less than 502.4kg
At least once every 6 months50 to less than 50024kg
Automatic leak detection required500 or more240kg

Sources: GOV.UK, Checking F gas equipment for leaks and GOV.UK, Qualifications to work with F gas

When to call an engineer

If a code returns after a restart, or it is anything from the outdoor unit table, book a diagnosis. Be Cool's F-Gas certified engineers have worked on commercial air conditioning across London and the South East since 2004, and our air conditioning repair service covers Mitsubishi Heavy Industries cassettes, ducted units and wall units. Note the code, the model number and whether it appeared in heating or cooling before you call.

Frequently asked questions

What does E5 mean on a Mitsubishi Heavy Industries air conditioner?

On PAC units, MHI lists E5 as a poor connection of the wiring between the indoor and outdoor units during operation, or communication disturbed by electrical noise. A defective outdoor PCB or a blown fuse can also cause it.

What does E9 mean on a Mitsubishi Heavy cassette?

E9 is drain trouble: a defective drain pump, a broken drain pump wire, a disconnected connector or a float switch malfunction.

What does E57 mean on Mitsubishi Heavy Industries?

MHI lists E57 as a shortage in refrigerant quantity or a service valve left closed. It needs a qualified engineer.

My SRK wall unit is flashing. How do I read it?

Count the flashes of the RUN or TIMER light and note what the other light is doing, then match the pattern to MHI's table above. Seven RUN flashes with the TIMER light on, for example, means insufficient refrigerant or a closed service valve.

Are Mitsubishi Heavy Industries and Mitsubishi Electric codes the same?

No. They are different manufacturers with different code lists. If your unit is Mitsubishi Electric, see our Mitsubishi Electric error codes guide instead.

Get the family right first

With Mitsubishi Heavy Industries, the first question is not "what does E19 mean" but "which family is this unit". Answer that, read the code against the right table, and most faults point an engineer straight at the right part. For other brands, see our error code library.

About the author: Ali Elm runs Be Cool Refrigeration & Air Conditioning, a family-run London firm that has been installing, servicing and repairing commercial refrigeration and air conditioning since 2004. His F-Gas certified team has delivered more than 2,000 projects across London and the South East.

Last updated: 2 November 2026

Ali Elm, Head of Operations at Be Cool Refrigeration

Written by

Ali Elm

Ali is the Head of Operations at Be Cool Refrigeration with over a decade of hands-on experience in HVAC and commercial refrigeration. He oversees every installation, repair, and maintenance project, making sure the work meets the highest standards. Ali holds full F-Gas certification and has worked across residential, commercial, and industrial refrigeration systems throughout London and the South East. When he is not on site, he writes these guides to help business owners and homeowners understand their cooling systems better.