On Danfoss ERC 21X controllers, A01 is a high temperature alarm, meaning the air in the cabinet is too warm. E29 means the air temperature sensor is defective or disconnected, and E27 the same for the evaporator sensor. On the ERC 112, E01 to E04 are sensor failures on inputs S1 to S4. On EKC 202D, EKC 302D and AK-CC 210 controllers, A1 is a high temperature alarm and E1 a controller fault.
Danfoss uses different code formats on different controllers, so start by finding the controller's model name. The tables below come from Danfoss's own manuals for each one.
At a glance
| Code | Controller | What Danfoss says it means |
|---|---|---|
| A01 | ERC 21X | High temp alarm: air temperature in cabinet is too high |
| A02 | ERC 21X | Low temp alarm: air temperature in cabinet is too low |
| E29 | ERC 21X | Air temperature sensor is defect or electrical connection is lost |
| A61 | ERC 21X | Condenser temp. too high, check air flow |
| E01, E02 | ERC 112 | S1 or S2 sensor failure |
| A1 | EKC, AK-CC 210 | High temperature alarm |
| E1 | EKC, AK-CC 210 | Faults in the controller |
Source: Danfoss ERC 21X and ERC 112 user guides, and the EKC 202D/302D and AK-CC 210 manuals.
How Danfoss shows an alarm
On the ERC 21X, Danfoss's controller documentation says the display alternates between the air temperature and the codes of any active alarms, with the alarm bell shown, until the alarm is resolved.
On the EKC 202D, EKC 302D and AK-CC 210, the LEDs on the front flash and the alarm relay activates. Pushing the top button shows the alarm report, and pushing again scrolls through several. Danfoss explains a useful difference between the two kinds of code: A alarms only appear once a set time delay has passed, while E alarms appear the moment the error occurs, and an A alarm stays hidden while an E alarm is active.
ERC 21X codes
Danfoss says the ERC 211, 213 and 214 are typically used in glass door merchandisers, commercial fridges and freezers, and cold rooms.
| Code | Alarm | What Danfoss says it means |
|---|---|---|
| E29 | Sair sensor error | Air temperature sensor is defect or electrical connection is lost |
| E27 | Def sensor error S5 | Evaporator sensor is defect or electrical connection is lost |
| E30 | Sc sensor error | Condenser sensor is defect or electrical connection is lost |
| A01 | High temp alarm | Air temperature in cabinet is too high |
| A02 | Low temp alarm | Air temperature in cabinet is too low |
| A99 | High Volt alarm | Supply voltage is too high (compressor protection) |
| AA1 | Low Volt alarm | Supply voltage is too low (compressor protection) |
| A61 | Condenser alarm | Condenser temp. too high, check air flow |
| A80 | Cond. block alarm | Condenser temp. too high, manual reset of alarm required |
| A04 | Door alarm | Door has been open for too long |
| A15 | DI Alarm | External alarm from DI input |
| A45 | Standby Alarm | Control has been stopped by r12 Main switch |
| Err | The temperature cannot be displayed due to a sensor error |
Some displays are messages rather than alarms: Pud means a pull-down cycle has started, Loc and UnL that the keyboard is locked or unlocked, PS that an access code is needed, OFF and On that control has been stopped or started with the main switch, and Fac that the controller has been reset to factory settings.
A01 on a Danfoss controller
A01 is the most searched Danfoss code. It means the cabinet air is warmer than the high alarm limit set in the controller. It is not a fault in itself, but a sign that something has stopped the cabinet holding temperature, such as a door left open, a heavy warm load, a blocked condenser or a fault in the refrigeration system. Check the door and the load first. If A61 or A80 appears alongside it, the condenser is running too hot, and if it returns with the door shut and the cabinet loaded normally, it needs an engineer.
ERC 112 codes
The ERC 112 uses short text codes. These come from Danfoss's ERC 112 user guide.
| Code | What Danfoss says it means |
|---|---|
| Hi | Air temperature is higher than the high alarm limit for the set delay |
| Lo | Air temperature is lower than the low alarm limit for the set delay |
| Con | Condenser temperature is too high or too low |
| dor | Door open for longer than the set time |
| uHi | Line voltage is higher than the set limit |
| uLo | Line voltage is lower than the set limit |
| LEA | Compressor running continuously for longer than the set time |
| E01 | S1 sensor failure |
| E02 | S2 sensor failure |
| E03 | S3 sensor failure |
| E04 | S4 sensor failure |
What each sensor does depends on how the controller has been configured, so an engineer will check which probe is on the input in alarm. The ERC 112 also shows status messages that are not faults: dEF for defrosting, Eco for Eco mode, SC for pull-down (super-chill) mode and HoL for holiday mode. unP and Prg mean the device is unprogrammed or has not finished programming, and its relay output stays locked until it is.
EKC 202D, EKC 302D and AK-CC 210 codes
These controllers share one alarm list, from Danfoss's EKC 202D and 302D manual and its AK-CC 210 user guide.
| Code | What Danfoss says it means |
|---|---|
| A1 | High temperature alarm |
| A2 | Low temperature alarm |
| A4 | Door alarm |
| A5 | Information. Parameter o16 is expired (maximum hold time) |
| A15, A16 | Alarm. Signal from DI1 or DI2 input |
| A45 | Standby position (stopped refrigeration via r12 or DI input) |
| A59 | Case cleaning. Signal from DI1 or DI2 input |
| A60 | High-temperature alarm for the HACCP function (AK-CC 210) |
| E1 | Faults in the controller |
| E6 | Fault in real-time clock. Check the battery or reset the clock (EKC 202). Reset the clock (EKC 302) |
| E25 | Sensor error on S3 |
| E26 | Sensor error on S4 |
| E27 | Sensor error on S5 |
| -d- | Defrost in progress, or first cooling after defrost |
| non | The defrost temperature cannot be displayed. Defrost stops on time |
On the EKC, Danfoss says that if the signal from a defined S3 or S4 sensor is lost, emergency cooling takes over and regulation continues using a recorded average cut-in frequency. That keeps the case cold for a while, but not under proper control. Danfoss also notes that -d- can stay on the display for up to 15 minutes after cooling resumes following a defrost, which is normal.
E0, E1, E2 and E8
Older lists of Danfoss codes often include E0, E2 and E8 as sensor faults. These codes do not appear in any of the four Danfoss manuals we checked. E1 does, but on the EKC and AK-CC 210 it means a fault in the controller itself, not a sensor. On the ERC 112, the sensor faults are E01 to E04, with a zero, which is easy to misread as E1 or E2.
How to acknowledge and reset a Danfoss alarm
- ERC 112. Danfoss's user guide says the display flashes the alarm message, and pressing any button acknowledges it.
- EKC and AK-CC 210. A short push on the upper button cuts out the alarm relay and shows the alarm code. Several alarms sit in a rolling list, which the uppermost or lowermost button scrolls through.
- ERC 21X A80. The condenser block alarm needs a manual reset, which Danfoss says can be done by setting r12 Main switch off and on again, or by powering the controller down.
Acknowledging an alarm silences it but does not fix the cause. Most temperature and sensor alarms clear once the condition does.
What you can check safely
- The door. A01, A1, Hi and the door alarms often follow a door left open or not closing properly.
- The condenser. With A61, A80 or Con, Danfoss's advice is to check the air flow and clean the condenser.
- The load. Make sure the cabinet is not overloaded with warm stock and that the air can circulate.
- Standby. A45 means control has been stopped by the main switch setting or a digital input, so check nobody has switched the controller to standby.
- The compressor. Danfoss's ERC 112 guide notes that a compressor that will not start may simply be waiting on its delay timer or a defrost, or seeing a supply voltage that is too low or too high.
Safety
Danfoss's ERC 112 guide warns that the inputs are not galvanically isolated and are connected directly to the mains supply, so door switches, sensors and their cables must meet reinforced insulation requirements. That is a good reason to leave sensor and wiring work to an engineer. Danfoss also warns that resetting to factory settings overwrites the original settings, which on a configured controller can change how the cabinet runs. Work on the refrigerant circuit needs an engineer with the F gas qualifications set out by GOV.UK.
When to call an engineer
- Any sensor error: E27, E29 or E30 on the ERC 21X, E01 to E04 on the ERC 112, or E25 to E27 on the EKC.
- E1 on an EKC or AK-CC 210, which points to the controller itself.
- A80, or A61 that returns after the condenser has been cleaned.
- A01 or A1 that returns with the door shut and a normal load.
- Repeated high or low voltage alarms, which may point to the supply.
Our commercial refrigeration repair team works on Danfoss-controlled cabinets, counters and cold rooms across London. If a cabinet is running but not cold, our guide to commercial fridges that stop cooling covers the usual causes.
Questions people ask about Danfoss error codes
What does A01 mean on a Danfoss controller?
On the ERC 21X, A01 is a high temperature alarm: the air temperature in the cabinet is too high. Check the door, the load and the condenser. If it keeps returning, the refrigeration system needs an engineer.
What is error E29 on a Danfoss?
E29 on the ERC 21X is an air temperature sensor error. Danfoss says the sensor is defective or its electrical connection has been lost, so the controller cannot read the cabinet temperature. It needs an engineer.
What does E02 mean on a Danfoss ERC 112?
E02 is a failure of the sensor on input S2. The display blinks E02, and if configured, the alarm relay cuts in and the buzzer sounds. What that sensor measures depends on how the controller is set up.
What does E1 mean on a Danfoss controller?
On the EKC 202D, EKC 302D and AK-CC 210, E1 means faults in the controller itself, not a sensor fault. On the ERC 112, the equivalent sensor code is E01, which is the S1 sensor.
What does A45 mean on a Danfoss?
A45 is a standby alarm. Refrigeration has been stopped through the r12 main switch setting or a digital input, so the cabinet is not cooling because it has been told to stop, not because of a fault.
How do I reset a Danfoss alarm?
Press any button on an ERC 112, or give the upper button a short push on an EKC or AK-CC 210, to acknowledge it. Most alarms clear when the cause does. The ERC 21X condenser block alarm A80 needs the main switch setting cycling off and on, or the power cycling.
Keeping a Danfoss cabinet on temperature
Find the controller model, read the code against the right table, and check the door, load and condenser first. Sensor faults and repeat alarms need an engineer, and planned refrigeration maintenance keeps condensers clean and sensors checked before they trigger an alarm.
Last updated: 4 November 2026

Written by
Ali Elm
Ali is the Head of Operations at Be Cool Refrigeration with over a decade of hands-on experience in HVAC and commercial refrigeration. He oversees every installation, repair, and maintenance project, making sure the work meets the highest standards. Ali holds full F-Gas certification and has worked across residential, commercial, and industrial refrigeration systems throughout London and the South East. When he is not on site, he writes these guides to help business owners and homeowners understand their cooling systems better.