
Gree error codes are two characters on the indoor unit's display. E codes are mostly system protections such as high or low pressure and communication, F codes are sensor faults or frequency limits, H, P and U codes cover the compressor, power module and electronics, and E6 is the communication fault.
Gree builds a wide range of air conditioners, and its code lists are not identical across them. That is the main trap with Gree codes. A code that means one thing on one series can be a normal status message on another. For this 2026 update we rebuilt the tables below from Gree's own service manuals, and where two Gree manuals disagree we say so.
At a glance
| Question | Answer |
|---|---|
| Where does the code show? | On the indoor unit's two-digit ("dual-8") display |
| Communication fault | E6, communication malfunction |
| Refrigerant-related | F0, refrigerant insufficient protection (Gree lists a refrigerant leak among the possible causes) |
| Pressure protection | E1, high pressure protection of system; E3, low pressure protection of system |
| Not a fault on the Livo Gen4 | E9 (cold air prevention) and E2 (anti-freezing protection for the evaporator), which Gree calls status codes |
| Service mode | Fo, refrigerant recovery mode, operated by the engineer for maintenance |
Source: Gree Livo Gen4 service manual, 9.1 Error Code List
Gree error code list
This is the error code list from Gree's service manual for its Livo Gen4 wall-mounted range, with what the unit does when the code appears. Codes are shown on the indoor unit's dual-8 display.
| Code | What Gree says it means | What the unit does |
|---|---|---|
| E1 | High pressure protection of system | Cooling: all loads stop except the indoor fan. Heating: the complete unit stops |
| E3 | Low pressure protection of system | Shows E3 until the low pressure switch stops operation |
| E4 | High discharge temperature protection of compressor | Compressor and outdoor fan stop in cooling; all loads stop in heating |
| E5 | Overcurrent protection | Compressor and outdoor fan stop in cooling; all loads stop in heating |
| E6 | Communication malfunction | Compressor stops in cooling; complete unit stops in heating |
| E8 | High temperature resistant protection | Compressor stops in cooling; complete unit stops in heating |
| EE | EEPROM malfunction | Compressor stops in cooling; complete unit stops in heating |
| EU | Limit/decrease frequency due to high temperature of module | Keeps running at reduced compressor frequency |
| C5 | Malfunction protection of jumper cap | Remote receiver works but commands are not carried out |
| F0 | Refrigerant insufficient protection, cut off protection of refrigerant | Compressor and outdoor fan stop in cooling; unit stops in heating |
| F1 | Indoor ambient temperature sensor open/short circuited | Indoor unit runs, other loads stop in cooling; unit stops in heating |
| F2 | Indoor evaporator temperature sensor open/short circuited | Stops when it reaches the set temperature in cooling; unit stops in heating |
| F3 | Outdoor ambient temperature sensor open/short circuited | Compressor stops in cooling; complete unit stops in heating |
| F4 | Outdoor condenser temperature sensor open/short circuited | Compressor stops in cooling; complete unit stops in heating |
| F5 | Outdoor discharge temperature sensor open/short circuited | Compressor stops after about 3 minutes |
| F6 | Limit/decrease frequency due to overload | Keeps running at reduced frequency |
| F8 | Decrease frequency due to overcurrent | Keeps running at reduced frequency |
| F9 | Decrease frequency due to high air discharge | Keeps running at reduced frequency |
| FH | Limit/decrease frequency due to antifreezing | Keeps running at reduced frequency |
| PH | Voltage for DC bus-bar is too high | Compressor stops in cooling; complete unit stops in heating |
| PL | Voltage of DC bus-bar is too low | Compressor stops in cooling; complete unit stops in heating |
| P0 to P3 | Compressor minimum, rated, maximum and intermediate frequency in test state | Shown during an engineer's test run, not a fault |
| P5 | Overcurrent protection of phase current for compressor | Compressor stops in cooling; complete unit stops in heating |
| PU | Charging malfunction of capacitor | Compressor stops in cooling; complete unit stops in heating |
| P7 | Malfunction of module temperature sensor circuit | Compressor stops in cooling; complete unit stops in heating |
| P8 | Module high temperature protection | Compressor stops in cooling; complete unit stops in heating |
| H3 | Overload protection for compressor | Compressor stops in cooling; complete unit stops in heating |
| H5 | IPM protection | Compressor stops in cooling; complete unit stops in heating |
| H6 | Internal motor (fan motor) does not operate | Fans, compressor and heater stop |
| H7 | Desynchronising of compressor | Compressor stops in cooling; complete unit stops in heating |
| L3 | Outdoor DC fan motor malfunction | Compressor stops |
| L9 | Power protection | Compressor and outdoor fan stop, then restart after a delay |
| LP | Indoor unit and outdoor unit do not match | Compressor and outdoor fan will not work |
| LC | Failure start-up | Compressor stops in cooling; complete unit stops in heating |
| U1 | Malfunction of phase current detection circuit for compressor | Compressor stops in cooling; complete unit stops in heating |
| U3 | Malfunction of voltage dropping for DC bus-bar | Compressor stops in cooling; complete unit stops in heating |
| U5 | Malfunction of complete unit's current detection | Compressor stops in cooling; complete unit stops in heating |
| U7 | The four-way valve is abnormal | Complete unit stops if it happens in heating |
| U8 | Malfunction of zero-cross detection circuit | Complete unit stops |
| JF | Malfunction of detecting plate (Wi-Fi) | Runs normally but cannot be controlled by the app |
| Fo | Refrigerant recovery mode | Operated by the engineer for maintenance |
| oE | Undefined outdoor unit error | Compressor and outdoor fan stop in cooling; unit stops in heating |
Source: Gree Livo Gen4 service manual, 9.1 Error Code List
Look at how many of those say the compressor stops in cooling but the whole unit stops in heating. That pattern matters in winter. A unit that seems to die completely on a cold morning may be throwing the same code it shrugged off with the fan still running all summer.
Where Gree ranges disagree
Gree's manual for its Livo Plus range lists several codes differently, and a few that the Livo Gen4 table does not have at all. If you have a different Gree model, check its own manual before trusting any single list, this one included.
| Code | Livo Plus manual | Livo Gen4 manual |
|---|---|---|
| E2 | Anti-freezing protection | Anti-freezing protection for evaporator, a status code, not an error |
| H1 | Defrosting | Not listed |
| H4 | Anti-high temperature protection | Not listed |
| HC | PFC protection | Not listed |
| F0 | Refrigerant leakage protection | Refrigerant insufficient protection, cut off protection of refrigerant |
| Fo | Gathering refrigerant | Refrigerant recovery mode |
| LU | Frequency limiting (power) | Not listed |
Sources: Gree Livo Plus service manual, 9.1 Error Code List and the Livo Gen4 manual above
Gree's own note on the Livo Plus table points out that F0 and Fo differ only by whether the "o" sits in the bottom half of the display segment. On a small, dim display that is easy to misread, and the two mean very different things: one is a refrigerant fault, the other is an engineer pumping the system down on purpose.
What you can check, and what needs an engineer
The frequency-limit codes (EU, F6, F8, F9, FH) mean the unit is still running but holding itself back. Gree's possible causes for those include overload and, for FH, poor air return or a low indoor fan speed, so a clean filter and clear airflow around both units is a fair first step. JF is a Wi-Fi board issue and leaves the unit working by remote. P0 to P3 and Fo only appear during service work.
The rest point at pressure, refrigerant, the compressor, the power module or the boards. That is engineer work, and the refrigerant side is regulated. GOV.UK puts it plainly: "You must have your own qualifications to work on equipment containing F gas, even if you work for someone else." Anyone offering to "just top it up" after an F0 without finding the leak is not doing the job, and may not be qualified to do it at all.
| Code group | Reasonable first check | Needs a qualified engineer |
|---|---|---|
| EU, F6, F8, F9, FH | Clean filters, clear airflow at both units | If it persists |
| JF | Use the remote; re-pair the app | If the Wi-Fi board needs replacing |
| E6, LP | Confirm both units have power | Yes, wiring and board checks |
| E1, E3, F0 | Switch off and leave it | Yes, refrigerant circuit work under F gas rules |
| F1 to F5, P7, U1, U3, U5, U8 | None | Yes, sensor and board testing |
| E4, E5, H3, H5, H7, P5, P8, PH, PL, PU, LC | Note when it happens | Yes, compressor and inverter diagnosis |
Sources: code meanings and causes from the Gree Livo Gen4 service manual; qualification rule from GOV.UK, Qualifications to work with F gas
When to call an engineer
If the code comes back after a restart, or it is a pressure, refrigerant or compressor code, it needs diagnosing on site. Be Cool's F-Gas certified engineers have worked on air conditioning across London and the South East since 2004, and our air conditioning repair service covers Gree units along with the other major brands. If the unit is cooling poorly without a code, our guide to an air conditioner not cooling is a better starting point.
Frequently asked questions
What does E6 mean on a Gree air conditioner?
Gree lists E6 as a communication malfunction between the indoor and outdoor units. The compressor stops in cooling and the whole unit stops in heating.
What does F0 mean on a Gree air conditioner?
On the Livo Gen4, F0 is refrigerant insufficient protection. Gree's list of possible causes includes closed valves, sensor problems, a blocked capillary or expansion valve, and a refrigerant leak, so it needs an engineer.
Is H1 a fault on a Gree unit?
On Gree's Livo Plus range, H1 is defrosting, which is normal in heating mode. Check your model's manual, because not every Gree table lists it.
What is E1 on a Gree air conditioner?
E1 is high pressure protection of the system. Gree's possible causes include too much refrigerant, poor heat exchange from a dirty coil or bad airflow, and a high ambient temperature.
Why does my Gree show P0, P1, P2 or P3?
Those show the compressor running at set frequencies during a test. You will normally only see them while an engineer is commissioning or testing the unit.
Match the code to the model
Gree's codes are detailed, and the "what the unit does" column is often as useful as the code itself. The catch is that the lists change between ranges. Take the model number off the indoor unit's label, check it against the right manual, and if you are unsure, give your engineer the code exactly as it appears. Our error code library has guides for the other brands.
About the author: Ali Elm runs Be Cool Refrigeration & Air Conditioning, a family-run London firm that has been installing, servicing and repairing commercial refrigeration and air conditioning since 2004. His F-Gas certified team has delivered more than 2,000 projects across London and the South East.
Last updated: 2 November 2026

Written by
Ali Elm
Ali is the Head of Operations at Be Cool Refrigeration with over a decade of hands-on experience in HVAC and commercial refrigeration. He oversees every installation, repair, and maintenance project, making sure the work meets the highest standards. Ali holds full F-Gas certification and has worked across residential, commercial, and industrial refrigeration systems throughout London and the South East. When he is not on site, he writes these guides to help business owners and homeowners understand their cooling systems better.