Gree Air Conditioner Error Codes: Full List and Meanings (2026)

Gree Air Conditioner Error Codes: Full List and Meanings (2026)
Ali ElmAC Error Codes

Gree error codes are two characters on the indoor unit's display. E codes are mostly system protections such as high or low pressure and communication, F codes are sensor faults or frequency limits, H, P and U codes cover the compressor, power module and electronics, and E6 is the communication fault.

Gree builds a wide range of air conditioners, and its code lists are not identical across them. That is the main trap with Gree codes. A code that means one thing on one series can be a normal status message on another. For this 2026 update we rebuilt the tables below from Gree's own service manuals, and where two Gree manuals disagree we say so.

At a glance

QuestionAnswer
Where does the code show?On the indoor unit's two-digit ("dual-8") display
Communication faultE6, communication malfunction
Refrigerant-relatedF0, refrigerant insufficient protection (Gree lists a refrigerant leak among the possible causes)
Pressure protectionE1, high pressure protection of system; E3, low pressure protection of system
Not a fault on the Livo Gen4E9 (cold air prevention) and E2 (anti-freezing protection for the evaporator), which Gree calls status codes
Service modeFo, refrigerant recovery mode, operated by the engineer for maintenance

Source: Gree Livo Gen4 service manual, 9.1 Error Code List

Gree error code list

This is the error code list from Gree's service manual for its Livo Gen4 wall-mounted range, with what the unit does when the code appears. Codes are shown on the indoor unit's dual-8 display.

CodeWhat Gree says it meansWhat the unit does
E1High pressure protection of systemCooling: all loads stop except the indoor fan. Heating: the complete unit stops
E3Low pressure protection of systemShows E3 until the low pressure switch stops operation
E4High discharge temperature protection of compressorCompressor and outdoor fan stop in cooling; all loads stop in heating
E5Overcurrent protectionCompressor and outdoor fan stop in cooling; all loads stop in heating
E6Communication malfunctionCompressor stops in cooling; complete unit stops in heating
E8High temperature resistant protectionCompressor stops in cooling; complete unit stops in heating
EEEEPROM malfunctionCompressor stops in cooling; complete unit stops in heating
EULimit/decrease frequency due to high temperature of moduleKeeps running at reduced compressor frequency
C5Malfunction protection of jumper capRemote receiver works but commands are not carried out
F0Refrigerant insufficient protection, cut off protection of refrigerantCompressor and outdoor fan stop in cooling; unit stops in heating
F1Indoor ambient temperature sensor open/short circuitedIndoor unit runs, other loads stop in cooling; unit stops in heating
F2Indoor evaporator temperature sensor open/short circuitedStops when it reaches the set temperature in cooling; unit stops in heating
F3Outdoor ambient temperature sensor open/short circuitedCompressor stops in cooling; complete unit stops in heating
F4Outdoor condenser temperature sensor open/short circuitedCompressor stops in cooling; complete unit stops in heating
F5Outdoor discharge temperature sensor open/short circuitedCompressor stops after about 3 minutes
F6Limit/decrease frequency due to overloadKeeps running at reduced frequency
F8Decrease frequency due to overcurrentKeeps running at reduced frequency
F9Decrease frequency due to high air dischargeKeeps running at reduced frequency
FHLimit/decrease frequency due to antifreezingKeeps running at reduced frequency
PHVoltage for DC bus-bar is too highCompressor stops in cooling; complete unit stops in heating
PLVoltage of DC bus-bar is too lowCompressor stops in cooling; complete unit stops in heating
P0 to P3Compressor minimum, rated, maximum and intermediate frequency in test stateShown during an engineer's test run, not a fault
P5Overcurrent protection of phase current for compressorCompressor stops in cooling; complete unit stops in heating
PUCharging malfunction of capacitorCompressor stops in cooling; complete unit stops in heating
P7Malfunction of module temperature sensor circuitCompressor stops in cooling; complete unit stops in heating
P8Module high temperature protectionCompressor stops in cooling; complete unit stops in heating
H3Overload protection for compressorCompressor stops in cooling; complete unit stops in heating
H5IPM protectionCompressor stops in cooling; complete unit stops in heating
H6Internal motor (fan motor) does not operateFans, compressor and heater stop
H7Desynchronising of compressorCompressor stops in cooling; complete unit stops in heating
L3Outdoor DC fan motor malfunctionCompressor stops
L9Power protectionCompressor and outdoor fan stop, then restart after a delay
LPIndoor unit and outdoor unit do not matchCompressor and outdoor fan will not work
LCFailure start-upCompressor stops in cooling; complete unit stops in heating
U1Malfunction of phase current detection circuit for compressorCompressor stops in cooling; complete unit stops in heating
U3Malfunction of voltage dropping for DC bus-barCompressor stops in cooling; complete unit stops in heating
U5Malfunction of complete unit's current detectionCompressor stops in cooling; complete unit stops in heating
U7The four-way valve is abnormalComplete unit stops if it happens in heating
U8Malfunction of zero-cross detection circuitComplete unit stops
JFMalfunction of detecting plate (Wi-Fi)Runs normally but cannot be controlled by the app
FoRefrigerant recovery modeOperated by the engineer for maintenance
oEUndefined outdoor unit errorCompressor and outdoor fan stop in cooling; unit stops in heating

Source: Gree Livo Gen4 service manual, 9.1 Error Code List

Look at how many of those say the compressor stops in cooling but the whole unit stops in heating. That pattern matters in winter. A unit that seems to die completely on a cold morning may be throwing the same code it shrugged off with the fan still running all summer.

Where Gree ranges disagree

Gree's manual for its Livo Plus range lists several codes differently, and a few that the Livo Gen4 table does not have at all. If you have a different Gree model, check its own manual before trusting any single list, this one included.

CodeLivo Plus manualLivo Gen4 manual
E2Anti-freezing protectionAnti-freezing protection for evaporator, a status code, not an error
H1DefrostingNot listed
H4Anti-high temperature protectionNot listed
HCPFC protectionNot listed
F0Refrigerant leakage protectionRefrigerant insufficient protection, cut off protection of refrigerant
FoGathering refrigerantRefrigerant recovery mode
LUFrequency limiting (power)Not listed

Sources: Gree Livo Plus service manual, 9.1 Error Code List and the Livo Gen4 manual above

Gree's own note on the Livo Plus table points out that F0 and Fo differ only by whether the "o" sits in the bottom half of the display segment. On a small, dim display that is easy to misread, and the two mean very different things: one is a refrigerant fault, the other is an engineer pumping the system down on purpose.

What you can check, and what needs an engineer

The frequency-limit codes (EU, F6, F8, F9, FH) mean the unit is still running but holding itself back. Gree's possible causes for those include overload and, for FH, poor air return or a low indoor fan speed, so a clean filter and clear airflow around both units is a fair first step. JF is a Wi-Fi board issue and leaves the unit working by remote. P0 to P3 and Fo only appear during service work.

The rest point at pressure, refrigerant, the compressor, the power module or the boards. That is engineer work, and the refrigerant side is regulated. GOV.UK puts it plainly: "You must have your own qualifications to work on equipment containing F gas, even if you work for someone else." Anyone offering to "just top it up" after an F0 without finding the leak is not doing the job, and may not be qualified to do it at all.

Code groupReasonable first checkNeeds a qualified engineer
EU, F6, F8, F9, FHClean filters, clear airflow at both unitsIf it persists
JFUse the remote; re-pair the appIf the Wi-Fi board needs replacing
E6, LPConfirm both units have powerYes, wiring and board checks
E1, E3, F0Switch off and leave itYes, refrigerant circuit work under F gas rules
F1 to F5, P7, U1, U3, U5, U8NoneYes, sensor and board testing
E4, E5, H3, H5, H7, P5, P8, PH, PL, PU, LCNote when it happensYes, compressor and inverter diagnosis

Sources: code meanings and causes from the Gree Livo Gen4 service manual; qualification rule from GOV.UK, Qualifications to work with F gas

When to call an engineer

If the code comes back after a restart, or it is a pressure, refrigerant or compressor code, it needs diagnosing on site. Be Cool's F-Gas certified engineers have worked on air conditioning across London and the South East since 2004, and our air conditioning repair service covers Gree units along with the other major brands. If the unit is cooling poorly without a code, our guide to an air conditioner not cooling is a better starting point.

Frequently asked questions

What does E6 mean on a Gree air conditioner?

Gree lists E6 as a communication malfunction between the indoor and outdoor units. The compressor stops in cooling and the whole unit stops in heating.

What does F0 mean on a Gree air conditioner?

On the Livo Gen4, F0 is refrigerant insufficient protection. Gree's list of possible causes includes closed valves, sensor problems, a blocked capillary or expansion valve, and a refrigerant leak, so it needs an engineer.

Is H1 a fault on a Gree unit?

On Gree's Livo Plus range, H1 is defrosting, which is normal in heating mode. Check your model's manual, because not every Gree table lists it.

What is E1 on a Gree air conditioner?

E1 is high pressure protection of the system. Gree's possible causes include too much refrigerant, poor heat exchange from a dirty coil or bad airflow, and a high ambient temperature.

Why does my Gree show P0, P1, P2 or P3?

Those show the compressor running at set frequencies during a test. You will normally only see them while an engineer is commissioning or testing the unit.

Match the code to the model

Gree's codes are detailed, and the "what the unit does" column is often as useful as the code itself. The catch is that the lists change between ranges. Take the model number off the indoor unit's label, check it against the right manual, and if you are unsure, give your engineer the code exactly as it appears. Our error code library has guides for the other brands.

About the author: Ali Elm runs Be Cool Refrigeration & Air Conditioning, a family-run London firm that has been installing, servicing and repairing commercial refrigeration and air conditioning since 2004. His F-Gas certified team has delivered more than 2,000 projects across London and the South East.

Last updated: 2 November 2026

Ali Elm, Head of Operations at Be Cool Refrigeration

Written by

Ali Elm

Ali is the Head of Operations at Be Cool Refrigeration with over a decade of hands-on experience in HVAC and commercial refrigeration. He oversees every installation, repair, and maintenance project, making sure the work meets the highest standards. Ali holds full F-Gas certification and has worked across residential, commercial, and industrial refrigeration systems throughout London and the South East. When he is not on site, he writes these guides to help business owners and homeowners understand their cooling systems better.