Polar Fridge and Freezer Error Codes: ER1 to ER5, HI, SO and SC

Polar Fridge and Freezer Error Codes: ER1 to ER5, HI, SO and SC
Ali ElmRefrigeration

On Polar U-Series fridges and freezers, ER1, ER2, ER3 and ER5 are probe faults, ER4 means the door is not closed properly, and SO and SC mean the cabinet probe is open or short-circuited. HI on these models means the condenser is above 60°C, not that the cabinet is too warm. Many Polar G-Series cabinets show no error codes at all, and HA and P1 are controller codes used by Dixell, not Polar.

The tables below come from Polar's own instruction manuals for its U-Series and G-Series fridges and freezers, published by UK suppliers. Check the model number on the rating plate before acting on a code.

At a glance

CodeWhat Polar says it meansWhat to do first
ER1The evaporator inlet probe is faultyPress any button to stop the alarm, then call a technician
ER2The evaporator return gas probe is faultyPress any button to stop the alarm, then call a technician
ER3The defrost probe (evaporator temperature probe) is faultyPress any button to stop the alarm, then call a technician
ER4Door not closed properly or door switch is faultyClose the door properly or have the door switch checked
ER5Condenser probe is faultyPress any button to stop the alarm, then call a technician
SOCabinet temperature probe is open-circuitedPress any button to stop the alarm, then call a technician
SCCabinet temperature probe is short-circuitedPress any button to stop the alarm, then call a technician
HICondenser temperature exceeding 60°CClean the condenser filter straight away, then power off and restart

Source: Polar U-Series refrigerators and freezers instruction manual, UA001 to UA004, troubleshooting table.

Polar U-Series codes in Polar's words

Polar's instruction manual for the UA001 to UA004 lists each code with an audible alarm.

CodeProbable causeSolution
ER1 and alarmThe evaporator inlet probe is faultyPress any button to cease alarm. Call a Polar agent or qualified technician to replace the faulty probe
ER2 and alarmThe evaporator return gas probe is faultyPress any button to cease alarm. Call a Polar agent or qualified technician to replace the faulty probe
ER3 and alarmThe defrost probe (evaporator temperature probe) is faultyPress any button to cease alarm. Call a Polar agent or qualified technician to replace the faulty probe
ER4 and alarmDoor not closed properly or door switch is faultyPress any button to cease alarm. Close the door or doors properly, or check the door switch
ER5 and alarmCondenser probe is faultyPress any button to cease alarm. Call a Polar agent or qualified technician to replace the faulty probe
SO and alarmCabinet temperature probe is open-circuitedPress any button to cease alarm. Call a Polar agent or qualified technician to replace the faulty probe
SC and alarmCabinet temperature probe is short-circuitedPress any button to cease alarm. Call a Polar agent or qualified technician to replace the faulty probe
HI and alarmCondenser temperature exceeding 60°CPower off and restart the machine to cease the alarm. Press the power button for 1 second to check the condenser temperature on the screen. Clean the condenser filter immediately, or call a Polar agent or qualified technician

HI on a Polar fridge

HI catches people out, because on most controllers it means the cabinet is too warm. On Polar's U-Series, it means the condenser has gone above 60°C, which usually means the condenser filter is clogged or the unit cannot get rid of its heat. Polar says the condenser needs monthly cleaning. On these models it sits above the cabinet at the top, with a removable filter that can be taken out and cleaned with a vacuum cleaner. Switch off and unplug before you do it.

Polar G-Series cabinets and counters

Polar's G-Series upright fridge and freezer manual and its stainless steel counter manual list no error codes, only a table of faults, causes and fixes. The only display messages in the upright manual are PON and POF, which show when the keypad is unlocked or locked by pressing two buttons together for 3 seconds. Neither is a fault.

HA, P1 and other codes

Many people search for what HA or P1 means on a Polar freezer. Neither appears in the Polar manuals we checked. Both are standard codes on Dixell controllers, where HA is a maximum temperature alarm and P1 a room or thermostat probe failure, so if your cabinet shows them, it may be fitted with a Dixell-type controller. Our guide to Dixell error codes covers those, but check the controller's name and the manual for your model, because Polar has not published them as its own codes.

Codes such as EE, EA, PF1, PF2, E1, E2 and E13 also do not appear in the Polar manuals we checked.

When a Polar fridge or freezer is not cooling

Polar's troubleshooting tables give these causes and fixes:

ProblemPossible causeWhat Polar says to do
The unit is not workingNot switched on, damaged plug or lead, blown fuse, power supply, or internal wiring faultCheck it is plugged in and switched on, replace the fuse, check the supply, or call a technician for the lead or wiring
The appliance is not coolingCoolant leak, fan motor failed, airflow to the condenser obstructed, or condenser cloggedIncrease the gap around the appliance, clean the condenser, or call a technician for a leak or fan
Temperature too high or too lowToo much ice on the evaporator, condenser blocked with dust, doors not shut properly, near a heat source, room too hot, unsuitable or hot food stored, or overloadedDefrost, clean the condenser, check the doors and seals, move it somewhere cooler or better ventilated, remove hot food or blockages to the fan, and reduce the load

For a wider list of causes, our guide to commercial fridges that stop cooling covers what to check across brands.

Defrosting and cleaning

  • Condenser. Polar says the condenser needs monthly cleaning, and that failing to clean it will reduce the unit's performance and life and may invalidate the warranty.
  • Defrost. Polar cabinets defrost automatically, every six hours on the G-Series counters. The upright manual also says to defrost the appliance at least every 3 months, more often if needed, and both ranges have a manual defrost button.
  • Power off first. Always switch off and disconnect the power before cleaning or routine maintenance.

Safety

  • Polar's manuals say a qualified technician must carry out repairs.
  • Do not use mechanical devices or other means to speed up defrosting, other than those recommended by the manufacturer, and do not damage the refrigerant circuit.
  • Do not use jet or pressure washers on the appliance, use it outside, or use electrical appliances inside the food compartments.
  • Polar warns that these cabinets are not for storing medical supplies.
  • The appliance must be earthed, and the U-Series manual carries a warning of risk of fire from flammable materials.

When to call an engineer

  • ER1, ER2, ER3, ER5, SO or SC. Polar's fix for each is replacing the faulty probe.
  • ER4 when the door closes properly, which points to the door switch.
  • HI that returns after the condenser filter has been cleaned.
  • A cabinet that runs but will not cool, which Polar links to a coolant leak or failed fan motor.

Our commercial refrigeration repair team works on Polar fridges and freezers across London. If a cabinet is older and keeps failing, our guide to repairing or replacing a commercial fridge helps with the decision.

Questions people ask about Polar fridge codes

What does HI mean on a Polar fridge?

On Polar U-Series models, HI means the condenser temperature has gone above 60°C. Clean the condenser filter straight away, then power off and restart to clear the alarm. If it returns, call a technician.

What does HA mean on a freezer?

HA is not in the Polar manuals we checked. On Dixell controllers, HA is a maximum temperature alarm, meaning the cabinet has been warmer than its alarm limit. Check the door and the load, and see our Dixell guide for more.

What does ER1 mean on a Polar fridge?

ER1 means the evaporator inlet probe is faulty. Press any button to stop the alarm, then call a Polar agent or qualified technician to replace the probe.

What does ER4 mean on a Polar freezer?

ER4 means the door is not closed properly or the door switch is faulty. Close the door or doors fully. If the alarm continues with the door shut, the switch needs checking.

What does P1 mean on a Polar fridge?

P1 does not appear in Polar's manuals. On Dixell controllers it means a room or thermostat probe failure, so if your cabinet shows P1 it is likely using that type of controller and needs a technician to check the probe.

How do I reset a Polar fridge alarm?

For ER and S codes, Polar says to press any button to stop the alarm. For HI, power the machine off and restart it. The code will come back if the fault is still there.

Keeping a Polar cabinet cold

Most Polar problems come back to the same few things: a clean condenser, a door that closes and a cabinet that is not overloaded or next to a heat source. Clean the condenser monthly, as Polar asks, and call a technician for probe faults, leaks and failed fans. Planned refrigeration maintenance covers the condenser cleaning if you would rather not do it yourself.

Last updated: 4 November 2026

Ali Elm, Head of Operations at Be Cool Refrigeration

Written by

Ali Elm

Ali is the Head of Operations at Be Cool Refrigeration with over a decade of hands-on experience in HVAC and commercial refrigeration. He oversees every installation, repair, and maintenance project, making sure the work meets the highest standards. Ali holds full F-Gas certification and has worked across residential, commercial, and industrial refrigeration systems throughout London and the South East. When he is not on site, he writes these guides to help business owners and homeowners understand their cooling systems better.