R410A Phase-Out UK: What It Means for Your Air Conditioning System

R410A Phase-Out UK: What It Means for Your Air Conditioning System
Ali ElmAC Maintenance

R410A is not banned in the UK. Since 1 January 2025, new single split air conditioners holding less than 3 kg of refrigerant cannot be placed on the GB market with R410A, and HFC supply tightens again on 1 January 2027. An existing R410A system is legal to run, repair and service with new gas, and there is no date by which you must replace it.

Most of the confusion comes from mixing up two sets of rules. The EU rewrote its F gas regulation in 2024 with much faster cuts, and a lot of online advice quotes it as if it applied here. It does not apply in England, Scotland or Wales. Great Britain still runs on its own retained version of the 2014 regulation, and in May 2026 the government confirmed it would not change the next step before it lands.

Here is where things actually stand in November 2026, and what it means for the system on your wall.

R410A at a glance: Great Britain, November 2026

QuestionAnswer
Is R410A banned?No. It is banned in new single split systems under 3 kg, not in existing systems
Can an existing R410A system be serviced?Yes, with virgin or recycled R410A. The servicing ban only covers gases with a GWP of 2,500 or more
What changes on 1 January 2027?The HFC quota for Great Britain falls from 31% to 24% of the 2009 to 2012 baseline
Will the government make that cut deeper?Not in 2026. Defra confirmed on 15 May 2026 that the existing 2027 step stands
What is R410A's GWP?2,088
What replaces it in new systems?Mainly R32 (GWP 675), with R454B (GWP 466) and propane (R290) in some equipment
Does Northern Ireland follow the same rules?No. Northern Ireland is part of the EU F gas system

What R410A is, and why it is being squeezed out

R410A is a blend of two hydrofluorocarbons, HFC-32 and HFC-125, and for the best part of two decades it was the standard refrigerant in split air conditioning and heat pumps. It is efficient, stable and non-flammable, which is why it replaced R22 so completely.

The problem is its global warming potential. GOV.UK lists the GWP of R410A as 2,088, meaning a kilogram released into the atmosphere has the warming effect of 2,088 kilograms of carbon dioxide over a hundred years. Nothing about that makes it dangerous to the people in the building. It is purely a climate measure, and every F gas rule in this article follows from that one number.

The dates that matter in Great Britain

1 January 2025: new single split systems

The retained F gas regulation bans placing on the market "single split air-conditioning systems containing less than 3 kg of fluorinated greenhouse gases" that use a gas with a GWP of 750 or more, from 1 January 2025. R410A, at 2,088, is caught. So is R407C.

A single split is one indoor unit connected to one outdoor unit. The GOV.UK bans table lists what falls outside it: larger air conditioning and heat pump systems such as chillers and larger splits, single splits used solely to cool products (which count as refrigeration), air-to-water single split systems and units on ships. Multi-splits and VRF systems are not covered by this ban.

"Placing on the market" means the first time a product is supplied in Great Britain. The Environment Agency's guidance, published through the industry body ACRIB, confirms that stock released for free circulation before 1 January 2025 can still be sold. You may still see an R410A single split for sale. That is legal, but it is old stock, and it is not something we would recommend buying now.

Servicing: no ban on R410A

There is a servicing ban, and it is often misread. Since 2020, virgin F gases with a GWP of 2,500 or more cannot be used to service refrigeration equipment holding 40 tonnes of CO2 equivalent or more. Recycled or reclaimed gas above that threshold can still be used until 2030, according to NetRegs.

That ban was aimed at R404A (GWP 3,922) and R507A (GWP 3,985) in commercial refrigeration. R410A sits below the threshold, so virgin R410A can still be used to service air conditioning in Great Britain, and nothing currently in law changes that.

1 January 2027: the quota step

The phase-down works on supply, not on equipment. Producers and importers get quota measured in CO2 equivalent, and the total allowed onto the GB market falls in steps against the 2009 to 2012 baseline.

PeriodHFC quota (% of baseline)
2015100%
2016 to 201793%
2018 to 202063%
2021 to 202345%
2024 to 202631%
2027 to 202924%
2030 onwards21%

Defra consulted in late 2025 on making the schedule steeper from 2027 and adding further steps out to 2050. On 15 May 2026 it confirmed that "we will not legislate in 2026 to change the phasedown steps from 1 January 2027", so the existing step applies. Cutting quota from 31% to 24% is still a reduction of 22.6% overnight, and the move to 21% in 2030 takes off another 12.5%. Defra has said more work is needed on longer-term reform, and as of November 2026 the formal outcome of the consultation has not been published.

Northern Ireland and the EU rules

Under the Windsor Framework, Northern Ireland is part of the EU F gas system, so EU Regulation 2024/573 applies there rather than the GB rules above. The EU version phases HFCs out of its market entirely by 2050 and brings in further equipment bans well ahead of anything in GB law.

If you read that R410A, or every F gas, is banned in new small air conditioners from 2027, check which rules the writer is describing. For a property in England, Scotland or Wales, that is the EU position, not the law that applies to you.

If you have an R410A system now

Keep using it. The ban applies to new products, not to equipment in service, and a well-maintained R410A system can run for many years yet. Replacing a healthy system early to get ahead of a rule that does not apply to it wastes good equipment.

What the law does require is that you look after it. GOV.UK's leak check guidance sets the frequency by the CO2 equivalent of the charge, and for R410A it translates like this:

R410A chargeCO2 equivalentLeak checks required
Under 2.4 kgUnder 5 tonnesNone required by the F gas rules (hermetically sealed units have a 10 tonne threshold)
2.4 kg to under 24 kg5 to under 50 tonnesAt least every 12 months
24 kg to under 240 kg50 to under 500 tonnesAt least every 6 months
240 kg or more500 tonnes or moreAutomatic leak detection must be fitted

Fitting automatic leak detection doubles the interval between checks. A typical single-room split sits below the first threshold. Multi-splits serving several rooms, and almost every VRF system, sit above it.

If a leak is found, the regulation is blunt: operators "shall ensure that the equipment is repaired without undue delay". Topping a system up and walking away is not a repair, and with R410A getting dearer it is also the most expensive way to run one. Regular air conditioning maintenance is where small leaks get caught before they become a recharge.

R410A prices and the quota

R410A will almost certainly keep getting dearer, though nobody can honestly give you a figure. Quota is counted in CO2 equivalent, so a high-GWP gas uses more of a supplier's allowance per kilogram than a low-GWP one. When the total allowance falls, suppliers put it towards the gases with the strongest demand and the best margin, and high-GWP blends lose out. NetRegs puts it simply: "The higher the GWP of a particular gas, the more expensive it will become."

Anyone who ran commercial refrigeration through the 2018 quota step remembers what that did to R404A. R410A is lower in GWP, so it should not be as dramatic, but the direction is the same. In practice, that means fixing leaks properly, keeping records of every top-up, and treating a large repeat leak on an older system as a reason to price a replacement. Our guide to the January 2027 HFC quota step goes into what that cut means across a whole estate.

What replaces R410A

RefrigerantGWPSafety classWhere you will find it
R32675A2L (lower flammability)The default in new single splits and many small heat pumps
R454B466A2L (lower flammability)Some larger air conditioning and heat pump systems designed around it
R290 (propane)Very low, not an F gasA3 (higher flammability)Monobloc heat pumps and some small sealed units

Defra's own assessment of the GB market describes "a significant transition away from the use of R-410A to HFC-32 and HFO/HFC blends", with propane use in small splits "very limited within Great Britain". R32 has a GWP of 675 and works at similar pressures to R410A, which is why manufacturers moved to it so quickly. For more on what it means in practice, see our guide to R32 refrigerant.

Chemours, which makes R454B as Opteon XL41, gives it a GWP of 466, a 78% reduction on R410A. Propane is a hydrocarbon rather than an F gas, so it sits outside the quota entirely. The trade-off is flammability, and Defra notes that the updated IEC 60335-2-40 standard allows up to 988 g of propane in a standard air conditioning system, which limits where it can be used.

None of these is a top-up for an R410A system. A different refrigerant means equipment designed for it.

If you are buying a new system

  • Single split for a room. It will be R32 or another gas under 750 GWP, because R410A is no longer allowed in new single splits. That decision has been made for you.
  • Multi-split or VRF. R410A is still legal in these in Great Britain, but with the 2027 step coming you would be buying into a shrinking supply for the life of the system. Ask for R32 or R454B equipment, and ask the installer to put the refrigerant and charge in the quote.
  • Heat pumps for heating. Monobloc air-to-water units on propane are worth a look, because they take the quota question off the table altogether.
  • Check the qualifications. R32 and R454B are mildly flammable, and propane more so. Installing and servicing them needs F gas certified engineers who work to the current safety standards.

Commercial systems

For businesses, the 2025 ban changes less than the quota does. Most commercial air conditioning is multi-split, VRF or chilled water, none of which is caught by the single split ban, and much of it runs on R410A with charges well above the leak check thresholds.

Three things are worth doing now. Get an accurate register of every system, its refrigerant and its charge in kilograms and CO2 equivalent. Make sure leak checks and records are up to date, because those duties apply today whatever happens to quota. And plan replacements of the oldest, leakiest systems on your own timetable rather than waiting for a failure in a heatwave. Our F gas regulations guide for businesses covers the operator duties in full.

Questions people ask about the R410A phase-out

Is R410A banned in the UK?

No. In Great Britain, R410A has been banned in new single split air conditioners holding less than 3 kg of refrigerant since 1 January 2025, but existing systems are legal to run and service, and R410A is still allowed in larger new systems such as multi-splits and VRF. Northern Ireland follows the stricter EU rules.

When is R410A being phased out?

There is no single end date in Great Britain. R410A is gradually squeezed by the HFC quota, which falls from 31% to 24% of the baseline on 1 January 2027 and to 21% in 2030. Defra has consulted on deeper cuts but confirmed in May 2026 that it will not change the 2027 step.

Can I still get R410A for my air conditioning?

Yes, an F gas certified engineer can still buy and use virgin or recycled R410A to service your system. You cannot buy it yourself, because the F gas regulation says these gases "shall only be sold to and purchased by undertakings that hold the relevant certificates". Expect the price to rise as quota tightens.

Is R410A being banned for servicing in 2026 or 2027?

No. The servicing ban applies to virgin gases with a GWP of 2,500 or more in refrigeration equipment holding 40 tonnes of CO2 equivalent or more. R410A's GWP is 2,088, so it is not affected, and no new servicing ban is in law in Great Britain.

What refrigerant replaces R410A?

In new single split air conditioners it is mostly R32, with a GWP of 675. Some larger systems use R454B, with a GWP of 466, and propane (R290) is used in monobloc heat pumps and some small sealed units. Each needs equipment designed for it.

Can I put R32 in an R410A system?

No. R32 is a different refrigerant with different flammability and charge characteristics, and an R410A system is not designed or rated for it. Keep servicing the R410A system with R410A, and move to R32 when the equipment itself is replaced.

Do I have to replace my R410A air conditioning?

No. There is no requirement to replace a working R410A system. Keep it maintained, have any leak repaired properly, and plan the replacement for when it reaches the end of its life or starts needing repeated refrigerant work.

Plan it, do not panic about it

The two mistakes we see are ripping out a perfectly good R410A system because of a headline, and specifying new R410A equipment because it is what has always been fitted. If you would like a straight view on a system you have now, or on what a replacement should run on, you can ask us for a quote and we will put the refrigerant and charge in writing.

Last updated: 4 November 2026

Ali Elm, Head of Operations at Be Cool Refrigeration

Written by

Ali Elm

Ali is the Head of Operations at Be Cool Refrigeration with over a decade of hands-on experience in HVAC and commercial refrigeration. He oversees every installation, repair, and maintenance project, making sure the work meets the highest standards. Ali holds full F-Gas certification and has worked across residential, commercial, and industrial refrigeration systems throughout London and the South East. When he is not on site, he writes these guides to help business owners and homeowners understand their cooling systems better.